What is the By-pass factor for cooling coil, if td1 = temperature at entry, td2 = temperature at exit and td3 = coil temperature?

What is the By-pass factor for cooling coil, if td1 = temperature at entry, td2 = temperature at exit and td3 = coil temperature? Correct Answer td2 – td3 / td1 – td3

By-pass factor is the amount of air by-passed in the process. So, for cooling coil, BPF = Temperature difference between exit and coil / Temperature difference between entry and coil = td2 – td3 / td1 – td3.