A plate condenser of dimensions l * b has been designed to be kept with side l in the vertical position. However due to oversight during erection and installation, it was fixed with side b vertical. How would this affect the heat transfer? Assume laminar conditions and same thermos-physical properties and take b = l/2

A plate condenser of dimensions l * b has been designed to be kept with side l in the vertical position. However due to oversight during erection and installation, it was fixed with side b vertical. How would this affect the heat transfer? Assume laminar conditions and same thermos-physical properties and take b = l/2 Correct Answer The condenser should be installed with shorter side vertical

h 1 = 0.943 0.25, h2 = 0.943 0.25. So, h 1/h 2 = 0.8409.