A plate condenser was designed to be kept vertical. How would the condensation coefficient be effected if due to site constraints, it has to be kept at 60 degree to the horizontal?

A plate condenser was designed to be kept vertical. How would the condensation coefficient be effected if due to site constraints, it has to be kept at 60 degree to the horizontal? Correct Answer 3.53% reduction in condensation coefficient

h VER = 0.943 0.25, h INC = 0.943 0.25.

Related Questions

A plate condenser of dimensions l * b has been designed to be kept with side l in the vertical position. However due to oversight during erection and installation, it was fixed with side b vertical. How would this affect the heat transfer? Assume laminar conditions and same thermos-physical properties and take b = l/2