Calculate the backwash pump required for the activated carbon filter for the following details. Flow: 1000 m3/h. Rise Velocity: 15m/h
Calculate the backwash pump required for the activated carbon filter for the following details. Flow: 1000 m3/h. Rise Velocity: 15m/h Correct Answer 1608 m3/hr
The area of the filter is calculated based on the flow rate and the rise velocity. Area of the filter is calculated as Flow/ Rise Velocity. Area= 1000/15 =67 m2. Backwash pump velocity is considered as 24 m/hr. Therefore the backwash pump required is area x velocity = 67 x 24= 1608 m3/hr.