When all three phases of a synchronous generator on no load are suddenly short circuited then symmetry of the short circuit current depends on which of the following?

When all three phases of a synchronous generator on no load are suddenly short circuited then symmetry of the short circuit current depends on which of the following? Correct Answer Instantaneous Voltage at which fault occurs

Symmetry of the short circuit current about time axis and DC offset depends upon the value of phase voltage at which short circuit occurs.

Related Questions

A 50 Hz synchronous generator is initially connected to a long lossless transmission line which is open circuited at the receiving end. With the field voltage held constant, the generator is disconnected from the transmission line. Which of the following may be said about the steady state terminal voltage and field current of the generator?