If the equivalent resistance and reactance of the transformer referred to the secondary of a single-phase transformer is 0.6 Ω and 0.8 Ω, respectively, the voltage drop in the transformer when supplying a current of 10 A at 0.8 pf lag is:
If the equivalent resistance and reactance of the transformer referred to the secondary of a single-phase transformer is 0.6 Ω and 0.8 Ω, respectively, the voltage drop in the transformer when supplying a current of 10 A at 0.8 pf lag is: Correct Answer 9.6 V
Concept:
[ alt="F2 Savita Engineering 16-6-22 D7" src="//storage.googleapis.com/tb-img/production/22/06/F2_Savita_Engineering_16-6-22_D7.png" style="width: 279px; height: 132px;">
The voltage drop across impedance 'Z' is given by:
VS - VR = IS (Rcosϕ ± Xsinϕ)
+ for lagging load and - for leading load
where VS - VR = Voltage drop
R = Resistance
X = Reactance
IS = Secondary side current
Calculation:
Given, IS = 10A
R = 0.6Ω
X = 0.8Ω
VS - VR = 10(0.6 × 0.8 + 0.8 × 0.6)
VS - VR = 9.6 V