If ouside air is to be conditioned from 60% relative humidity and 40 °C dry bulb temperature to 50% relative humidity and 24 °C dry bulb temperature, which psychromatic process would be required?

If ouside air is to be conditioned from 60% relative humidity and 40 °C dry bulb temperature to 50% relative humidity and 24 °C dry bulb temperature, which psychromatic process would be required? Correct Answer Cooling and dehumidification 

Explanation:

On moving from point 1to point 2 as shown in figure:

  • Specific Humidity decreases therefore Dehumidification
  • Dry bulb Temperature decreases therefore cooling

Process is Cooling and dehumidification.

[ alt="F1 Krupalu Maduri 13.01.2022 D11" src="//storage.googleapis.com/tb-img/production/22/01/F1_Krupalu_Maduri_13.01.2022_D11.png" style="width: 179px; height: 201px;">

Related Questions

The bypass factor (B.P.F.) in case of sensible heating of air is (Where td1 = Dry bulb temperature of air entering the heating coil, td2 = Dry bulb temperature of air leaving the heating coil and td3 = Dry bulb temperature of heating coil)
The bypass factor, in case of sensible cooling of air, is given by (where td1 = Dry bulb temperature of air entering the cooling coil, td2 = Dry bulb temperature of air leaving the cooling coil and td3 = Dry bulb temperature of the cooling coil)