A sustained three phase fault occurs in the power system shown in the figure. The current and voltage phasors during the fault (on a common reference), after the natural transients have died down, are also shown. Where is the fault located?
A sustained three phase fault occurs in the power system shown in the figure. The current and voltage phasors during the fault (on a common reference), after the natural transients have died down, are also shown. Where is the fault located? Correct Answer Point Q
Concept :
As shown in the phasor diagram
- Current I2 & I4 have phase difference of 180°. So that they cancel out each other.
- Magnitude of the current I1 is more than current I3. Also I1 is more lagging than I3
- So that fault is located at point Q.