A three phase transformer has a nameplate rating of 30 MVA, 230Y/69Y kV with a leakage -reactance of 10% and the transformer connection is wye-wye. Choosing a base of 30MVA and 230 kV on high voltage side, the high voltage side impedance ____________

A three phase transformer has a nameplate rating of 30 MVA, 230Y/69Y kV with a leakage -reactance of 10% and the transformer connection is wye-wye. Choosing a base of 30MVA and 230 kV on high voltage side, the high voltage side impedance ____________ Correct Answer 1763.3 Ω

On the high voltage side, Zb=kVb2/MVAb(3-ph) = 2302/30 = 1763.33 Ω.