A 3-phase balanced supply system is connected to a 3-phase unbalanced load. Power supplied to this load can be measured using: 1. two wattmeters 2. one wattmeter 3. three wattmeters Which of these statement/s is/are correct?
A 3-phase balanced supply system is connected to a 3-phase unbalanced load. Power supplied to this load can be measured using: 1. two wattmeters 2. one wattmeter 3. three wattmeters Which of these statement/s is/are correct? Correct Answer 1 and 3
Measurement of polyphase power: 3 - ϕ
1) For 3ϕ – 4 wire → neutral is present
2) As per Blondel’s theorem, if neutral is not present for ‘n’ wire system, then ‘n-1’ number of wattmeter’s are required for ‘n’ wire system.
|
Type of Load |
Star 3 - ϕ 3 - wire |
Star 3 - ϕ 4 – wire |
Delta 3 - ϕ 3 – wire |
|
Balanced |
2 |
1, 2, 3 |
2 |
|
Unbalnced |
2 |
2, 3 |
2 |
- The one-wattmeter method is used for the measurement of three-phase power in case balanced loads only
- It is used for both star and delta connected loads
- Two wattmeter method and three wattmeter methods are used for both balanced and unbalanced loads
- Two wattmeter method is best suitable for three-phase three-wire system and three wattmeter method is suitable for the three-phase four-wire system
Note: If neutral is available we shouldn’t use a 2 – wattmeter method.